EasyManua.ls Logo

York YLAA0115 - Page 52

York YLAA0115
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
52
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
SECTION 5 – TECHNICAL DATA
CHILLER
MODEL
VOLTAGE
CODE
MIN CKT.
AMPS
MIN N/F
DISC SW
MIN DUAL
ELEM
FUSE &
MIN CB
MAX DUAL
ELEM
FUSE
MAX CB
125
208 512 800 600 600
230 511 800 600 600
380 309 400 350 350
460 258 400 300 300
575 204 250 225 225
136
208 579 800 600 600
230 577 800 600 600
380 338 600 400 400
460 285 400 300 300
575 226 400 250 250
142
208 579 800 600 600
230 577 800 600 600
380 338 600 400 400
460 285 400 300 300
575 226 400 250 250
155
208 618 800 700 700
230 617 800 700 700
380 374 600 400 400
460 311 400 350 350
575 246 400 300 300
156
208 634 800 700 700
230 632 800 700 700
380 383 600 400 400
460 319 400 350 350
575 252 400 300 300
170
208 740 1000 800 800
230 738 1000 800 800
380 447 600 500 500
460 372 600 400 400
575 295 400 350 350
175
208 740 1000 800 800
230 738 1000 800 800
380 447 600 500 500
460 372 600 400 400
575 295 400 350 350
200
208 734 1000 800 800
230 731 1000 800 800
380 443 600 500 500
460 369 600 400 400
575 292 400 300 300
230
208 959 1200 1000 1000
230 956 1200 1000 1000
380 599 600 600 600
460 504 600 600 600
575 359 600 400 400
TABLE 10 - ELECTRICAL DATA WITHOUT PUMPS (CONT’D)