Cooling capacities
Model
Evap.
leaving
water
temp.
°C
DB air temperature at condenser intake °C
25 30 35 40 45
Capacity
Consump-
tion
Capacity
Consump-
tion
Capacity
Consump-
tion
Capacity
Consump-
tion
Capacity
Consump-
tion
W kW W kW W kW W kW W kW
YLCC-H
102
5 105 696 41.03 97 536 42.41 90 432 43.33 81 792 44.72 74 304 44.49
6 109 344 41.95 100 992 43.33 93 120 44.72 85 344 45.64 77 280 47.02
7 112 992 42.41 104 640 44.26 96 000 46.10 88 320 47.02 80 544 48.41
8 116 832 43.33 108 834 45.18 100 128 47.02 91 776 47.94 83 520 49.33
9 120 576 44.26 112 128 46.10 103 680 47.94 95 232 49.33 86 880 50.71
10 124 704 45.18 115 968
47.02 107 328 48.87 98 400 50.25 89 856 52.09
11 128 736 46.10 119 712 47.94 110 976 49.79 102 144 51.63 92 928 53.02
12 132 672
47.02 123 648 48.87 114 720 50.71 105 696 52.55 98 784 54.40
YLCC-H
122
5 118 911 50.94 109 730 52.66 101 720 53.81 92 018 55.52 83 594 55.24
6 123 015 52.09 113 620 53.81 104 763 55.52 96 015 56.67 86 942 58.38
7 127 120 52.66 117 723 54.95 108 000 57.24 99 363 58.38 90 615 60.10
8 131 440 53.81 121 935 56.10 112 647 58.38 103 251 59.53 93 963 61.25
9 135 652 54.95 126 148 57.24 116 643 59.53 107 140 61.25 97 743 62.96
10 140 296 56.10 130 467
58.38 120 750 60.67 110 703 62.39 101 090 64.68
11 144 832 57.24 134 680 59.53 124 850 61.82 114 915 64.11 104 547 65.83
12 149 260
58.38 139 108 60.67 129 070 62.96 118 911 65.25 111 135 67.54
YLCC-H
152
5 143 134 61.46 132 084 63.54 122 464 64.92 110 763 66.99 100 623 66.64
6 148 075 62.84 136 764 64.92 126 105 66.99 115 574 68.37 104 653 70.44
7 153 015 63.54 141 704 66.30 130 000 69.06 119 604 70.44 109 073 72.51
8 158 215 64.92 146 775 67.68 135 595 70.44 124 284 71.82 113 103 73.89
9 163 285 66.30 151 845 69.06 140 404 71.82 128 965 73.89 117 654 75.97
10 168 875
67.68 157 045 70.44 145 344 73.20 133 254 75.28 121 685 78.04
11 174 335 69.06 162 115 71.82 150 285 74.58 138 324 77.35 125 845 79.42
12 179 670
70.44 167 445 73.20 155 355 75.97 143 134 78.73 133 774 81.49
Note: The cooling and heating capacities on the tables are in accordance with a liquid temperature increase, in the indoor exchanger, of C
(t = 5° C). DB = Dry bulb. RH = Relative humidity.