33
A01 Antifreeze control set point temperature U 11 (R/W) °C - A07 5 5
A02 Antifreeze reset differential U 12 (R/W) °K 50 0.3 3 3
A03 Antifreeze alarm bypass temperature U 22 (R/W) Sec. 150 0 0 0
A04
Antifreeze heater activation temperature U 13 (R/W) °C r16 A01 5 5
A05
Antifreeze heater activation differential U 14 (R/W) °K 50 0.3 1 1
A06 F 6 (R/W) - 1 0 0 0
A07
Antifreeze control set point temperature, minimum limit U 15 (R/W) °C 79 -40 0 0
A08 U 16 (R/W) °C r15 A01 25 25
A09 U 17 (R/W) °C 50 0.3 3 3
A10 U 23 (R/W) 3 0 2 2
Automatic start for antifreeze alarm
0 = function deactivated
1 = water pump starts
2 = pump and compressor start in heating cycle (heat
pump only)
3 = heater in operation
Backup heater control probe
0 = control probe
1 = antifreeze probe
Heater deactivation set point differential temperature in
heating
Heater activation set point temperature in heating
H01 F 54 (R/W) 3 2
H02 F 12 (R/W) 1 1
H03 F 13 (R/W) 1 1
H04 F 55 (R/W) 3 3
F 56 (R/W) 3 0 1 1
H06 U 14 (R/W) 1 0 1 1
H07 U 15 (R/W) 1 0 1 1
H08 F 57 (R/W) 3 0 2 2
H09 U 16 (R/W) 1 0 1 1
H10 U 58 (R/W) 200 1 1 1
H11
Output configuration (no selectable) F 59 (R/W) 3 0 3 1
Parameters related to the unit configuration
Pump operation
0 = absent
1 = always operative
2 = ON upon demand of the control
3 = ON upon demand and time
Number of vent circuits (do not change this parameter)
Number of evaporating units present (do not change this
parameter)
Number of compressors per circuit (do not change this
parameter)
Digital intake COOL/HEAT
0 = absent. 1 = present
Digital intake ON/OFF
0 = absent. 1 = present
Network configuration (do not change this
parameter)
Keyboard lock
0 = disabled. 1 = enabled
Signal address for monitoring
0 = future use as a terminal
H05
Display Description
VS
Level Unit Max. Min.
Value
Pump Cool
Parameters related to the antifreeze control
Display Description
VS
Level Unit Max. Min.
Value
Pump Cool
Unit model. 2 = air-water chiller (YLCC)
3 = air-water pump (YLCC-H)