35
r01 Cool cycle temperature set point U 41 (R/W) °C r14 r13 12 12
r02 Cool temperature set point differential U 42 (R/W) °C 50 0.3 3 3
r03
Heat cycle temperature set point U 43 (R/W) °C r16 r15 40 40
r04
Heat cycle temperature differential U 44 (R/W) °C 50 0.3 3 3
r05 F 78 (R/W) 2 0 2 2
r06 F 79 (R/W) 4 0 0 0
r07 Neutral zone differential F 45 (R/W) °C 50 0 1 1
r08 F 80 (R/W) Sec. 999 r09 120 120
r09 F 81 (R/W) Sec. 999 c04 100 100
r10 F 82 (R/W) Sec. 999 r11 120 120
r11 F 83 (R/W) Sec. 999 c05 100 100
r12 (Only if r06 = 4) Compressor deactivation differential F 46 (R/W) °C 50 0 1 1
r13 Cool cycle minimum set point temperature U 47 (R/W) °C r14 -40 8 8
r14 Cool cycle maximum set point temperature U 48 (R/W) °C 80 r13 30 30
r15 Heat cycle minimum set point temperature U 49 (R/W) °C r16 -40 15 15
r16 Heat cycle minimum set point temperature U 50 (R/W) °C 80 r15 50 50
Parameters related to the controller
Compressor rotation
0 = Disabled
1 = FIFO type
2 = By run hours
Control type
0 = Proportional. Intake temperature
1 = Proportional + neutral zone. Intake temperature
2 = Proportional. Output temperature
3 = Proportional + neutral zone. Output temperature
4 = By time + dead zone. Output temperature (on chillers
only)
(Only if r06 = 4) Maximum activation time. Output tem-
perature
(Only if r06 = 4) Minimum activation time. Output tempera-
ture
(Only if r06 = 4) Maximum deactivation time. Output tem-
perature
(Only if r06 = 4) Minimum deactivation time. Output tem-
perature
Display Description
VS
Level Unit Max. Min.
Value
Pump Cool