/01 F 1 (R/W) - 1 0 1 1
/02 F 2 (R/W) - 1 0 1 1
/03 F 14 (R/W) - 2 0 1 0
/04/08 F - 3 0 1 0
/05 F 3 (R/W) - 1 0 0 0
/06 F 4 (R/W) - 1 0 1 0
/07 F 16 (R/W) - 2 0 1 0
/09 Minimum supply voltage F 18 (R/W) 0.01 Vdc /10 0 50 50
/10 Maximum supply voltage F 19 (R/W) 0.01 Vdc 500 /09 450 450
/11 Minimum pressure F 1 (R/W) bar /12 0 0 0
/12 Maximum pressure F 2 (R/W) bar 99.9 /11 34.5 34.5
/13 B1 probe calibration F 3 (R/W) °C 12 -12 0 0
/14 B2 probe calibration F 4 (R/W) °C 12 -12 0 0
/15 B3 probe calibration F 5 (R/W) °C 12 -12 0 0
/17/18 B5, B6 probe calibration F 6 (R/W) °C 12 -12 0 0
/19
B7 probe calibration F 9 (R/W) °C 12 -12 0 0
/16/20
B4, B8 probe calibration F 10 (R/W) bar 12 -12 0 0
/21 Digital filter U 20 (R/W) - 15 1 4 4
/22 Intake limitation U 21 (R/W) - 15 1 8 8
/23 Unit of measurement 0 = C; 1 = F U 5 (R/W) - 1 0 0 0
b00 Display read out probe (B1) U 24 (R/W) - 7 0 0 0
b01 Value read by probe B1, common water intake D 70 (R) °C - - -
b02 Value read by probe B2, water outlet circuit 1 D 71 (R) °C - - -
b03 Value read by probe B3, liquid circuit 1 D 72 (R) °C - - -
b04/05/08 Value read by probe B4 D 73 (R) °C/bar - - -
b06
Value read by probe B7, water outlet circuit 2 D 76 (R) °C - - -
b07
Value read by probe B8, liquid circuit 2 D 77 (R) bar - - -
Parameters related to probes
NTC B1 probe (water intake). 0 = absent (function not avai-
lable). 1 = present
NTC B2 probe (water outlet 1). 0 = absent (function not
available). 1 = present
NTC B6 probe (water outlet 2). 0 = absent, 1 = present
B4, B8 type probe, 0 = absent, 1 = ON/OFF, 2 = NTC, 3 =
5 Vdc ratiometric
NTC B7 probe (liquid 2). 0 = absent, 1 = present
Display Description
15 (R/W)
17 (R/W)
B5 type probe. 0 = absent (function not available).
1 = present
NTC B3 probe (liquid 1). 0 = absent, 1 = present
c01 Minimum ON time U 25 (R/W) Sec. 999 0 5 5
c02 Minimum OFF time U 26 (R/W) Sec. 999 0 10 10
c03 Time between starts of the same compressor U 27 (R/W) Sec. 999 0 360 360
c04 Time between starts of two compressors U 28 (R/W) Sec. 999 0 10 10
c05 Time between stops of two compressors U 29 (R/W) Sec. 999 0 10 10
c06 ON timing U 30 (R/W) Sec. 999 0 10 10
c07 Compressor start delay with regard to the pump U 31 (R/W) Sec. 150 0 20 20
c08 Pump OFF delay with regard to the compressor U 32 (R/W) Min. 150 0 20 20
c10/11 ON hour counter, compressors 1 and 2 D 90 (R) Hours 800 0 - -
c11/12 ON hour counter, compressors 3 and 4 D 91 (R) Hours 800 0 - -
c14 ON hour counter for compressor maintenance U 34 (R/W) Hours 100 0 0 0
c15
ON hour counter, pump D 94 (R/W) Hours 800 0 - -
c17
Minimum time between pump starts U 35 (R/W) Min. 150 0 15 15
c18
Minimum pump ON time U 36 (R/W) Min. 15 0 3 3
Display Description Level VS
Value
Pump Cool
Level
VS
Unit
Max. Min.
Value
Pump Cool
Parameters related to the compressor
Unit Max. Min.