Loading...
FORM 160.84-EG1 (617)
JOHNSON CONTROLS
35
EVAPORATOR
MODEL
EVAPORATOR
CONDENSER
MODEL
CONDENSER
1 PASS 2 PASS 3 PASS 1 PASS 2 PASS 3 PASS
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
EB3310-B
1170
(74)
4690
(296)
590
(37)
2350
(148)
390
(25)
1280
(81)
CC2508-D
560
(35)
2020
(127)
560
(35)
2020
(127)
710
(45)
2560
(162)
EB3310-C
1500
(95)
6010
(379)
750
(47)
3010
(190)
CC2508-E
700
(44)
2520
(159)
700
(44)
2520
(159)
EB3310-2
790
(50)
3140
(198)
390
(25)
1570
(99)
260
(16)
1050
(66)
CC2508-2
460
(29)
1640
(103)
460
(29)
1640
(103)
300
(19)
1100
(69)
EB3310-3
1400
(88)
5610
(354)
700
(44)
2800
(177)
CC2508-3
660
(42)
2380
(150)
660
(42)
2380
(150)
EB3314-B
1170
(74)
4690
(296)
590
(37)
2350
(148)
390
(25)
1340
(85)
CB2910-B
1160
(73)
4170
(263)
580
(37)
2090
(132)
390
(25)
1390
(88)
EB3314-C
1500
(95)
6010
(379)
750
(47)
3010
(190)
CB2910-C
1380
(87)
4980
(314)
690
(44)
2490
(157)
460
(29)
1660
(105)
EB3314-2
790
(50)
3140
(198)
390
(25)
1570
(99)
260
(16)
1050
(66)
CB2910-D
1620
(102)
5840
(368)
810
(51)
2920
(184)
540
(34)
1950
(123)
EB3314-3
1400
(88)
5610
(354)
700
(44)
2800
(177)
CB2910-E
1760
(111)
6330
(399)
880
(56)
3170
(200)
590
(37)
2110
(133)
EC3312-B
1280
(50)
5120
(198)
640
(25)
2560
(99)
430
(16)
1380
(66)
CB2910-F
1950
(123)
7030
(444)
980
(62)
3520
(222)
EC3312-C
1460
(50)
5830
(198)
730
(25)
2920
(99)
490
(16)
1570
(66)
CB2910-2
1420
(90)
5120
(323)
710
(45)
2560
(162)
470
(30)
1710
(108)
EC3312-D
1630
(50)
6500
(198)
810
(25)
3250
(99)
540
(16)
1750
(66)
CB2910-3
1740
(110)
6290
(397)
870
(55)
3140
(198)
EC3312-E
1830
(50)
7330
(198)
920
(25)
3660
(99)
CB2914-B
1160
(73)
4170
(263)
580
(37)
1920
(121)
390
(25)
1290
(81)
EC3312-2
1320
(50)
5270
(198)
660
(25)
2630
(99)
440
(16)
1760
(66)
CB2914-C
1380
(87)
4980
(314)
690
(44)
2270
(143)
460
(29)
1530
(97)
EC3312-3
1520
(50)
6070
(198)
760
(25)
3030
(99)
510
(16)
2020
(66)
CB2914-D
1620
(102)
5840
(368)
810
(51)
2630
(166)
540
(34)
1790
(113)
EC3312-4
1710
(50)
6840
(198)
850
(25)
3420
(99)
570
(16)
2280
(66)
CB2914-E
1760
(111)
6330
(399)
880
(56)
2830
(179)
590
(37)
1930
(122)
EC3312-5
1900
(50)
7610
(198)
950
(25)
3810
(99)
CB2914-F
1950
(123)
7030
(444)
980
(62)
3100
(196)
EC3314-B
1280
(50)
5120
(198)
640
(25)
2560
(99)
430
(16)
1380
(66)
CB2914-2
1420
(90)
5120
(323)
710
(45)
2560
(162)
470
(30)
1710
(108)
EC3314-C
1460
(50)
5830
(198)
730
(25)
2920
(99)
490
(16)
1570
(66)
CB2914-3
1740
(110)
6290
(397)
870
(55)
3140
(198)
580
(37)
2100
(132)
EC3314-D
1630
(50)
6500
(198)
810
(25)
3250
(99)
540
(16)
1750
(66)
CB3310-B
1590
(100)
5720
(361)
790
(50)
2860
(180)
530
(33)
1910
(121)
EC3314-E
1830
(50)
7330
(198)
920
(25)
3660
(99)
CB3310-C
1900
(120)
6830
(431)
950
(60)
3420
(216)
630
(40)
2280
(144)
EC3314-2
1320
(50)
5270
(198)
660
(25)
2630
(99)
440
(16)
1760
(66)
CB3310-D
2480
(156)
8940
(564)
1240
(87)
4370
(276)
830
(52)
2980
(188)
EC3314-3
1520
(50)
6070
(198)
760
(25)
3030
(99)
510
(16)
2020
(66)
CB3310-E
2760
(174)
9940
(627)
1380
(51)
4720
(298)
EC3314-4
1710
(50)
6840
(198)
850
(25)
3420
(99)
570
(16)
2280
(66)
CB3310-2
1620
(102)
5840
(368)
810
(61)
2920
(184)
540
(34)
1950
(123)
EC3314-5
1900
(50)
7610
(198)
950
(25)
3810
(99)
CB3310-3
1930
(122)
6960
(439)
970
(81)
3480
(220)
640
(40)
2320
(146)
Application Data (Cont'd)
TABLE 2 - WATER FLOW RATE LIMITS IN GPM (L/S) – BASED UPON STANDARD TUBES @ DESIGN FULL
LOAD CONDITIONS (CONT'D)