Loading...
FORM 160.84-EG1 (617)
JOHNSON CONTROLS
37
Application Data (Cont'd)
EVAPORATOR
MODEL
EVAPORATOR
CONDENSER
MODEL
CONDENSER
1 PASS 2 PASS 3 PASS 1 PASS 2 PASS 3 PASS
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
CB3314-E
2920
(163)
10540
(588)
1460
(81)
4310
(294)
CB3314-2
1940
(163)
7000
(588)
970
(81)
3500
(294)
650
(54)
2330
(196)
CB3314-3
2250
(163)
8120
(588)
1130
(81)
4060
(294)
750
(54)
2710
(196)
CB3314-4
2910
(163)
10490
(588)
1450
(81)
5120
(294)
CB3914-B
2840
(163)
10220
(588)
1420
(81)
4210
(294)
950
(54)
2970
(196)
CB3914-C
3210
(163)
11580
(588)
1610
(81)
4610
(294)
1070
(54)
3330
(196)
CB3914-D
3540
(163)
12740
(588)
1770
(81)
4930
(294)
CB3914-2
2650
(163)
9550
(588)
1330
(81)
4780
(294)
880
(54)
3180
(196)
CB3914-3
3160
(163)
11390
(588)
1580
(81)
5390
(294)
1050
(54)
3800
(196)
CB3914-4
3770
(163)
13580
(588)
1880
(81)
5960
(294)
TABLE 2 - WATER FLOW RATE LIMITS IN GPM (L/S) – BASED UPON STANDARD TUBES @ DESIGN FULL
LOAD CONDITIONS (CONT'D)