Recommended clearances for all units
For access to the unit control center, make sure that the unit is not higher when using spring
isolators.
Minimum clearances are shown in Figure 31 and are as follows:
- Side to wall: 6 ft (1.8 m)
- Rear to wall: 6 ft (1.8 m)
- Control panel end to wall: 4 ft (1.2 m)
- Top: No obstructions whatsoever
- Distance between adjacent units: 10 ft (3 m)
Figure 31: Unit clearance dimensions, ft (m)
Ensure that no more than one wall around the chiller yard is higher than the chiller.
Avoid locations near windows or structures where normal operating sounds might be
objectionable.
YVAM Air-Cooled Centrifugal Liquid Chiller26