6. When the Current Limit control Source is set to
BAS, 0-10, 4-20 or PWM, the BAS can control
the maximum allowable compressor motor AMPS
from 30 to 100%, through the Remote Current
Limit Setpoint. Refer to Figure 14 on page 13,
Figure 15 on page 13, and Figure 16 on page
13.
7. The Johnson Controls METASYS
System may
be interfaced with the chiller OptiView
Control
Center to provide unied chiller plant system con-
trol. The METASYS
System directly communi-
cates with the OptiView
Control Center via the
SC-EQ communication card which is installed in
the Control Center. All temperatures, pressures,
safety alarms and cycling information known to
the OptiView™ Control Center are then available
to the METASYS
System for integrated chiller
plant control, data logging, and local, remote op-
erator displays. The SC-EQ also allows the BAS
to start, stop, and reset the chillers leaving chilled
water setpoint and the current limit setpoint by
using the BACnet MS/TP protocol. The SC-EQ
also supports other BAS systems using BACnet
MS/TP, Modbus RTU or N2 communication pro-
tocols.