Table 8: Electrical data: single-phase gas heat, belt drive
ZE036-060 - Without Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Accessory
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
036
(3)
208-1-60 15.4 83.9 24 2.3 17.4 None - - - 39.5 50
230-1-60 15.4 83.9 24 2.3 17.4 None - - - 39.5 50
048
(4)
208-1-60 19.6 130 31 2.3 17.4 None - - - 44.2 60
230-1-60 19.6 130 31 2.3 17.4 None - - - 44.2 60
060
(5)
208-1-60 24.4 144.2 38 4.4 17.4 None - - - 52.3 70
230-1-60 24.4 144.2 38 4.4 17.4 None - - - 52.3 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZE036-060 - With Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Accessory
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
036
(3)
208-1-60 15.4 83.9 24 2.3 17.4 20 None - - - 49.5 60
230-1-60 15.4 83.9 24 2.3 17.4 20 None - - - 49.5 60
048
(4)
208-1-60 19.6 130 31 2.3 17.4 20 None - - - 54.2 70
230-1-60 19.6 130 31 2.3 17.4 20 None - - - 54.2 70
060
(5)
208-1-60 24.4 144.2 38 4.4 17.4 20 None - - - 62.3 80
230-1-60 24.4 144.2 38 4.4 17.4 20 None - - - 62.3 80
1. Minimum Circuit Ampacity.