Loading...
5742637-YIM-D-0620
Johnson Controls Ducted Systems 21
ZE036-060 - Without Powered Convenience Outlet (Direct Drive)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Accessory
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
036
(3.0)
208-1-60 15.4 83.9 24 2.3 6 0
NONE - - - 27.5 35
E05 4 1 19.2 31.5 40
E07 5.6 1 26.9 41.2 45
E10 8 1 38.5 55.6 60
E15 11.9 2 57.2 79 80
E20 15.9 2 76.4 103.1 110
230-1-60 15.4 83.9 24 2.3 6 0
NONE - - - 27.5 35
E05 5.3 1 22.1 35.1 40
E07 7.5 1 31.2 46.6 50
E10 10.6 1 44.2 62.7 70
E15 15.9 2 66.2 90.3 100
E20 21.2 2 88.3 117.9 125
208-3-60 10.4 73 16.3 2.3 6 0
NONE - - - 21.3 30
E05 4 1 11.1 21.4 30
E07 5.6 1 15.5 26.9 30
E10 8 1 22.2 35.3 40
E15 11.9 2 33 48.8 50
E20 15.9 2 44.1 62.7 70
230-3-60 10.4 73 16.3 2.3 6 0
NONE - - - 21.3 30
E05 5.3 1 12.7 23.4 30
E07 7.5 1 18 30.1 35
E10 10.6 1 25.5 39.4 40
E15 15.9 2 38.2 55.3 60
E20 21.2 2 51 71.2 80
048
(4.0)
208-1-60 19.6 130 30.5 2.3 7.6 0
NONE - - - 34.4 45
E05 4 1 19.2 34.4 45
E07 5.6 1 26.9 43.2 50
E10 8 1 38.5 57.6 60
E15 11.9 2 57.2 81 90
E20 15.9 2 76.4 105.1 110
230-1-60 19.6 130 30.5 2.3 7.6 0
NONE - - - 34.4 45
E05 5.3 1 22.1 37.1 45
E07 7.5 1 31.2 48.6 50
E10 10.6 1 44.2 64.7 70
E15 15.9 2 66.2 92.3 100
E20 21.2 2 88.3 119.9 125
208-3-60 13.7 83.1 21.4 2.3 7.6 0
NONE - - - 27 35
E05 4 1 11.1 27 35
E07 5.6 1 15.5 28.9 35
E10 8 1 22.2 37.3 40
E15 11.9 2 33 50.8 60
E20 15.9 2 44.1 64.7 70
230-3-60 13.7 83.1 21.4 2.3 7.6 0
NONE - - - 27 35
E05 5.3 1 12.7 27 35
E07 7.5 1 18 32.1 40
E10 10.6 1 25.5 41.4 45
E15 15.9 2 38.2 57.3 60
E20 21.2 2 51 73.2 80