Operating instructions Dcontrol Date 0730
TBL02_54-GB 0730 Part-No. 00153238-GB
Page 6 / 28
{ Maximum cross section for line and motor connection
PKDT5 / PKDM5..20: 2.5 mm
2
PKDM25/35 : 6 mm
2
PKDM25/35E: 10 mm
2
PKDM50/80 (E) : 35 mm
2
{ Stepless controlled output voltage approx. 20-100 % (line voltage)
Rampup time / Rampdown time for PKDM 5…35: ca. 5 sec
Rampup time / Rampdown time for PKDM 50/80: ca. 15 sec.
{ Minimum motor current
for PKDT5, PKDM5: 0.2 A
for PDKM10...80: 0.5 A
{ Input resistance for sensor or signal set for the rotational speed:
- For 0-10 V input: R
i
> 100 kΩ
- For 4-20 mA input: R
i
= 100 Ω
{ Voltage supply e.g. for sensors +24 V ±20 %, I
max
120 mA
{ Output (0-) 10 V, I
max
10 mA (short-circuit-proof)
- For function as speed controller: Fixed voltage 10 V for external potentiometer
- For function as a P-controller: 0-10 V proportional to the regulated output voltage
{ Max. permissible ambient temperature depending on version
- for controller with internal fuses type PKDT.. and PKDM..: 40° C (up to 55° C with derating)
- for without internal fuses type PKDM..E
und PKDM..Z : 50° (up to 55° C with derating)
{ Min. permissible ambient temperature 0° C (if mains voltage is not switched off up to -20°C)
{ Permissible installation height 0..4000m amsl above 1000 m amsl the rated current is to be reduced by
5% / 1000m
{ Permissible rel. humidity 85 %, no condensation
{ Electromagnetic compatibility for the standard voltage 230 / 400 V according to DIN IEC 60038
- Interference emission in accordance with EN 61000-6-3
- Interference immunity in accordance with EN 61000-6-2
{ Harmonics current EN 61000-3-2
The units comply with EN 61000-3-2 for a "professional unit". Up to a maximum current of
4 ampere the limits were complied without any qualification.
3.3 Versions
IP 54 for wall mounting
♦ PKDT5 Motor protection using thermostat connection, internal semiconductor fuses
♦ PKDT
5Z Motor protection using thermostat connection, semiconductor fuses construction site
♦ PKDM.. Motor protection using thermostat or thermistor connection.
♦ PKDM
..Z Motor protection using thermostat or thermistor connection, semiconductor fuses construction site
IP20 for switch cabinet mounting
♦ PKDM..E Motor protection using thermostat or thermistor connection, semiconductor fuses construction site