14.5.2 Block function
Blocks the controller if certain errors occur several times is succession. The errors must occur in
directly consecutive travel tests. The fault counter is set to 0 when performing a trouble-free run.
The following block functions can be set in the Monitoring / MOD_ST menu:
Fix 2 Sec.: No blocking function, the output congured on "ST" drops for 2 seconds during a
malfunction and then increases again (speed preset V_x must be switched off)
Lock n.3: Lock function after 3 malfunctions. Output "ST" remains dropped after the 3rd error
Lock n.2: Lock function after 2 malfunctions. Output "ST" remains dropped after the 2rd error
Lock n.1: Lock function after 1 malfunction1. Output "ST" remains dropped after the 1st error
Errors which lead to disabling of the ZETADYN 4 are marked by a dot in the S column.
14.5.3 Notes 0xx
Information about:
Error memory content
Changes in the operating conditions
Application of special frequency inverter functions
Note-No. Note text Description M S
N0 Memory empty EEPROM is empty
N010 Update software Software update was carried out
Additional information: Version of the new software
N020 MOT_TYP changed Motor type in "Motor name plate" was changed
N077 ST_LST: locked Five faults occurred in direct succession
Fault memory is blocked
Additional information: indicates the most recent fault
The fault counter is set to 0 when performing a trouble-free run.
N080 Mode: EVA ->Norm Switchover from evacuation to normal mode was implemented
N081 Mode: Norm ->EVA Switchover from normal to evacuation to mode was implemented
N082 Mode:ParaChange The parameter set was changed
N085 Mode: Safety Br Safety brake function was implemented
N086 Mode:Enc.Adj.MB Encoder-alignment with closed brakes was carried out
N087 Mode:Encoder-Adj. Manual encoder offset was carried out
N088 Mode:Encoder-Check The encoder offset alignment was checked
14.5.4 Error 1xx
Hardware conguration error
Software error
Error no. Error text Error cause M S
100 Serial no. missing
Frequency inverter/CU does not have a serial number, e.g. after a component
replacement
101 System-Error
A defective internal component was identied during a self-test of the fre-
quency inverter
110
120
CU: No ID
CU ID no. was not detected:
CU is not present or its ID EEPROM does not reply
111 CUSH: No ID
Shunt ID no. was not detected:
Shunt module is not present or its ID EEPROM does not reply
113
123
CUEE: No ID
ID no. of the extension card for the rotary encoder was not detected: extension
module is not present or its ID EEPROM does not reply
115
125
SP: No ID
Switching power supply ID no. was not detected: Switching power supply is not
present or its ID EEPROM does not reply
116
126
PP: No ID
Power print ID no. was not detected:
Power print is not present or its ID EEPROM does not reply
Translation of the original operating instructions
ZETADYN 4C Error diagnosis
R-TBA12_01-GB 1415 Part.-No. 00163371-GB
132
/204

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ZIEHL-ABEGG ZETADYN 4C and is the answer not in the manual?

ZIEHL-ABEGG ZETADYN 4C Specifications

General IconGeneral
BrandZIEHL-ABEGG
ModelZETADYN 4C
CategoryDC Drives
LanguageEnglish

Related product manuals