EasyManua.ls Logo

Zonecheck 450 - Technical Specifications; Zonecheck Unit Specifications; Circulation Pump Specifications; Flow-switch Specifications

Zonecheck 450
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Working Pressure Rating.......................................................
Operating Temperature Range...........................................
Pipe Diameter...........................................................................
Approvals......................................................................................
Water, 12 bar (175 psi) maximum
0°C - 49°C (32°F – 120°F)
50, 65, 80, 100, 150 & 200 mm (2, 2½ 3, 4, 6 & 8“)
LPCB, UL, FM and VdS
Zonecheck
The ‘Standby’ mode will not give any false alarms when fitted in conjunction with an approved water flow
alarm device.
Circulation Pump
Operating Voltage...................................................................
Full Load Current.....................................................................
Power Rating.............................................................................
IP Rating.....................................................................................
WP Rating...................................................................................
Capacitor...................................................................................
1~120v 60Hz
1.63A
185 W maximum
IP44
12 bar (175 psi)
5.0 µF/400 VDB
Key-switch
Mounting...................................................................................
Type...............................................................................................
Operating Voltage..................................................................
Internat Consumption.............................................................
Operation Modes....................................................................
LED Operation:
Standby (Ready state)..............................................................
Test Initiation:...........................................................................
Flow Switch Activation:.........................................................
Flush-mounting
ZCK-1E
Single-phase 220 V, 50 Hz
7.5 W Maximum
Self-test: Wired locally
Group test: Interconnected
No LED
‘Pump LED (green)
‘Water Flow’ LED (green)
Flow-switch
Type.............................................................................................
Contact Rating...................................................................................
IP Rating.....................................................................................
Contacts.....................................................................................
Triggering Flow Rate...................................................................
Working Pressure...................................................................
Time Delay.................................................................................
WFDE
10A @ 125/250 VAC; 2.5 A at 24 VDC
IP54
2 change-over contacts
30–57 l/min
17.25 bar (250 psi) maximum; 16 bar (VdS)
0 - 30 s
Specifications
10