I.S. BARRIER OR ISOLATOR
SAFE AREA
Installation Notes:
1. Barriers must be CSA Certified and/or NRTL approved
(as applicable) with entity parameters and must be
installed per manufacturer's instructions.
2. Control equipment connected to barrier inputs must
not use or generate more than 250 Vrms.
3. Installation must be in accordance with the Electrical
Code of the country in use.
4. The following entity conditions must be satisfied:
Voc < Vmax
Isc < Imax
Ca > Ci + Ccable
La > Li + Lcable