EasyManua.ls Logo

A.O. Smith BMS Interface - Parameter List

A.O. Smith BMS Interface
85 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Instruction manual - BMS Interface
4.1 Parameter list
Para-
meter
Register
type
Value
Type
Unit
Description
Conversion
y = first byte
x = second byte
Unit type
BFC
SGS
SGE
0
03
16 bits direct
Address
-
Actual Modbus address BMS Interface
-
Yes
Yes
Yes
1
03
16 bits direct
Temperature
°C
Temperature in the top of the water heater
x/100
Yes
Yes
Yes
2
03
16 bits direct
Temperature
°C
Temperature in the bottom of the water heater
x/100
Yes
Yes
Yes
3
03
16 bits direct
Temperature
°C
Flue gas sensor (dummy)
x/100
n.a.
n.a.
n.a.
4
03
16 bits direct
Temperature
°C
Set point water heater
x/100
Yes
Yes
Yes
5
03
16 bits direct
Delta T
K
Hysteresis up gas burner
x/256
Yes
Yes
Yes
6
03
16 bits direct
Delta T
K
Hysteresis down gas burner
x/256
Yes
Yes
Yes
7
03
16 bits direct
State
-
Unit state
-
Yes
Yes
Yes
8
03
16 bits direct
Relay
-
Relay: Potable water pump
1=Closed, 0=Open
Yes
Yes
Yes
9
03
16 bits direct
Burning hours
Hours
Burning hours water heater
-
Yes
Yes
Yes
10…14
03
16 bits direct
Error
-
Last 5 lock outs (internal codes)
-
Yes
Yes
Yes
15…19
03
16 bits direct
Error
-
Last 5 blocking errors (internal codes)
-
Yes
Yes
Yes
20
03
16 bits direct
Error
-
Actual error code (internal code)
-
Yes
Yes
Yes
21
03
16 bits direct
Relay
ON/OFF
Relay: External ON / OFF
1=Closed, 0=Open
Yes
Yes
Yes
22
03
16 bits direct
Solar State
-
State solar control
-
n.a.
Yes
Yes
23…27
03
16 bits direct
Error
-
Last 5 solar errors (internal codes)
-
n.a.
Yes
Yes
28
03
16 bits direct
Temperature
°C
Temperature solar collector (S1)
x/100
n.a.
Yes
Yes
29
03
16 bits direct
Temperature
°C
Solar temperature in the bottom of the tank (S2)
x/100
n.a.
Yes
Yes
30
03
16 bits direct
Temperature
°C
Solar temperature in the top of the storage tank (S3)
x/100
n.a.
Yes
n.a.