EasyManua.ls Logo

ABB 15VHK500 - Page 10

ABB 15VHK500
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB
IB
6.2
.
7.7
.
-
1
Page
10
ASEA
BROWN
BOVERI
rupter
to
emit
some
X
-
radiation
which
could
be
a
health
hazardon
prolonged
exposure
at
close
range
.
Accordingly
,
even
though
the
emission
is
low
and
on
for
such
a
short
period
of
time
,
it
is
considered
appropriate
to
exercise
caution
.
Therefore
,
do
not
run
any
primary
circuit
dielectric
with
-
stand
tests
on
isolated
interrupters
with
open
contacts
,
above
rated
voltage
unless
test
personnel
are
adequately
shielded
or
they
are
no
less
than
six
feet
from
the
test
unit
.
Regarding
complete
breakers
,
it
is
noted
that
NO
hazard
-
ous
X
-
radiation
is
produced
with
closed
contacts
at
any
test
voltage
or
with
open
contacts
at
rated
voltage
and
there
should
be
no
cause
for
concern
.
Further
,
if
the
breaker
is
tested
in
its
switchgear
compartment
,
the
enclosure
steel
provides
sufficient
shielding
to
protect
personnel
from
X
-
radiation
at
the
test
voltages
recommended
below
at
the
normal
distances
maintained
for
electrical
safety
.
The
following
test
values
should
be
used
for
dielectric
testing
the
complete
breaker
and
are
to
be
applied
for
a
one
-
minute
period
.
LUBRICATION
The
15
VHK
circuit
breakers
are
lubricated
during
factory
assembly
as
follows
:
1
.
All
mechanism
parts
,
bearings
,
pins
,
etc
.
,
have
been
lubricated
with
Anderol
757
manufactured
by
Nuodex
,
Inc
.
(
formerly
Tenneco
Chemical
,
Inc
.
)
.
(
ABB
No
.
71
2994
A
,
4
oz
.
tube
)
.
If
the
grease
should
become
contaminated
or
unduly
oxidized
(
hardened
and
darkened
)
or
if
parts
are
replaced
,
any
relubrication
should
be
done
with
the
lubricants
noted
.
NOTES
:
1
.
The
mechanism
should
be
periodically
inspected
for
lubrication
contamination
:
frequency
of
inspection
is
de
-
pendent
on
operating
environment
.
2
.
Do
not
use
light
oil
to
lubricate
any
mechanism
parts
.
In
emergency
situations
,
Anderol
732
may
be
used
as
a
temporary
lubricant
.
In
these
cases
,
allow
time
for
the
solvents
to
evaporate
prior
to
any
mechanical
operations
.
It
is
mandatory
that
the
breaker
undergo
thorough
lubrica
-
tion
with
Anderol
757
at
the
next
maintenance
interval
.
Use
of
solvents
to
free
contaminated
lubricant
is
strictly
forbid
-
den
without
immediate
relubrication
using
Anderol
757
.
Note
that
bearing
surfaces
must
be
repacked
a
this
will
require
disassembly
of
the
mechanism
.
Do
not
operate
t
circuit
breaker
without
completing
this
procedure
.
3
.
The
charging
motor
is
sealed
and
no
lubrication
is
required
.
60
Hz
Primary
Circuit
36.0
kV
Secondary
Circuit
(
Control
)
1100
V
«
»
If
it
is
desired
to
make
a
dielectric
test
on
the
secondary
control
wiring
,
turn
the
spring
charging
motor
disconnect
switch
(
1
,
Fig
.
3
)
to
the
OFF
"
position
.
Apply
test
voltage
(
1100
V
-
AC
)
for
one
minute
to
each
of
the
secondary
disconnect
contacts
at
the
rear
of
the
circuit
breaker
.
If
it
is
desired
to
make
a
dielectric
test
on
the
spring
charging
motor
,
turn
the
motor
disconnect
switch
(
1
,
Fig
.
3
)
to
the
ON
position
.
Apply
test
voltage
(
540
V
-
AC
)
for
one
minute
to
the
motor
circuit
.
DIELECTIRIC
TESTS
It
is
recommended
that
dielectric
withstand
tests
be
made
prior
to
use
and
then
at
routine
maintance
periods
to
verify
the
integrity
of
vacuum
interrupters
.
If
,
during
the
dielectric
withstand
test
,
the
required
test
voltage
cannot
be
sus
-
tained
across
the
open
contacts
of
the
vacuum
interrupter
,
the
interrupter
is
faulty
and
must
be
replaced
.
Always
insure
that
the
contact
air
gap
is
correct
betore
conducting
primary
circuit
dielectric
tests
.
ELECTRICAL
CHARACTERISTICS
OF
CONTROL
DEVICES
For
operating
voltage
ranges
for
various
nominal
control
voltages
,
refer
to
Table
1
.
For
average
current
values
at
various
nominal
control
voltages
,
refer
to
Table
2
.
The
current
values
given
in
this
table
are
average
.
,
steady
state
values
and
momentary
inrush
currents
for
all
charging
motors
and
AC
coils
are
approximately
six
to
eight
times
these
values
.
CAUTION
CAUTION
CAUTION
CAUTION
While
the
procedure
for
dielectric
testing
a
vacuum
breaker
is
similar
to
that
for
any
other
type
breaker
,
there
are
two
areas
which
require
extra
CAUTION
in
handling
.
1
.
The
internal
shield
of
a
vacuum
interruptercan
acquire
an
electrical
charge
which
is
usually
retained
even
after
the
voltage
is
removed
.
On
certain
types
of
interrupters
,
this
shield
is
attached
to
the
exposed
mid
-
band
ring
and
a
groun
-
ding
stick
should
be
used
to
discharge
the
ring
before
working
on
the
device
.
2
.
Dielectric
test
voltages
higher
than
rated
voltage
,
applied
across
open
contacts
,
may
cause
a
vacuum
inter
-
ELECTRICAL
OPERATING
SEQUENCE
Please
refer
to
the
specific
schematic
diagrams
and
other
operational
information
furnished
with
your
order
.
Fig
.
9
is
provided
as
a
typical
schematic
for
general
information
on
electrical
operation
.
Courtesy of NationalSwitchgear.com

Related product manuals