EasyManua.ls Logo

ABB 15VHK500 - Maintenance & Adjustments

ABB 15VHK500
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AM
IB
6.2
.
7.7
.
-
1
Page
6
ASEA
BROWN
BOVERI
open
the
breaker
as
required
.
Open
sliding
door
(
2
)
in
front
compartment
door
(
1
)
.
En
-
gage
racking
crank
(
4
)
and
push
racking
unlocking
lever
(
3
)
to
left
.
Rotate
racking
crank
(
4
)
counterclockwise
approxi
-
mately
1
/
4
turn
,
then
release
unlocking
lever
.
Continue
cranking
counterclockwise
until
racking
mechanism
auto
-
matically
stops
at
TEST
'
position
.
and
it
is
not
expected
that
the
interrupters
will
have
to
be
replaced
due
to
excessive
erosion
of
contacts
.
There
is
,
however
,
a
checkforcontact
wipe
(
contact
pressure
)
which
is
also
a
measure
ol
contact
erosion
.
This
check
is
covered
under
Circuit
Breaker
Operation
and
Contacts
.
When
contact
wipe
is
less
than
the
minimum
specified
and
it
has
been
determined
that
the
breaker
closes
fully
and
there
is
not
a
mechanical
problem
,
then
the
interrupter
should
be
replaced
due
to
contact
erosion
.
If
,
however
after
the
first
inspection
period
there
is
no
indication
of
any
problems
,
actual
operating
experience
with
specific
circuits
will
indicate
the
future
amount
of
maintenance
needed
for
the
various
circuit
breakers
and
the
procedure
can
be
modified
as
required
.
Ol
course
,
where
unusual
service
conditions
exist
,
as
covered
by
ANSI
Standard
C
37.04
,
it
must
be
presumed
that
these
conditions
were
considered
at
the
time
of
order
;
that
the
equipment
supplied
was
designed
for
the
special
application
;
and
that
an
appropriate
supplemental
mainte
-
nance
program
has
been
developed
.
These
maintenance
instructions
only
cover
circuit
breakers
used
under
the
standard
service
conditions
.
At
the
selected
maintenance
period
,
the
following
tests
and
adjustments
should
be
made
;
NOTE
:
The
following
tabulated
tests
and
adjustments
are
those
that
are
normally
necessary
for
proper
maintenance
and
operation
of
the
15
VHK
circuit
breaker
.
The
remaining
portions
of
the
breaker
close
coil
assembly
,
shunt
trip
device
,
control
relay
,
auxiliary
switch
and
motor
require
no
maintenance
during
the
standard
life
of
the
circuit
breaker
regardless
of
the
operating
duty
.
Repeat
same
operation
for
DISCONNECT
'
position
.
The
circuit
breaker
can
now
be
positioned
for
withdrawal
.
If
in
the
upper
compartment
the
lift
device
must
first
be
located
in
the
correct
position
.
For
withdrawal
from
the
switchboard
,
again
push
the
racking
unlocking
lever
to
the
left
and
turn
the
racking
crank
counterclockwise
only
until
resistance
to
motion
is
felt
.
(
Approximately
2
-
3
turns
DO
NOT
FORCE
.
)
The
closing
springs
,
if
charged
,
will
auto
-
matically
discharge
when
the
circuit
breaker
is
moved
to
the
withdrawn
position
.
The
circuit
breaker
can
now
be
re
-
moved
from
the
compartment
by
pulling
on
the
handle
located
on
the
front
barrier
.
MAINTENANCE
,
ADJUSTMENTS
AND
TESTS
General
Information
j
The
15
VHK
circuit
breakers
are
designed
for
minimum
maintenance
and
tested
to
insure
that
minimum
mainte
-
nance
will
be
required
.
The
few
adjustments
that
are
noted
are
required
only
when
an
operational
check
indicates
a
problem
.
Of
course
,
during
the
maintenance
checks
,
all
accessible
bolts
,
nuts
and
screws
should
be
routinely
checked
to
insure
that
they
are
tight
,
it
is
recommended
that
the
circuit
breaker
be
normally
inspected
after
the
first
2000
operations
,
regardless
of
the
type
of
duty
it
is
used
for
.
These
operations
can
be
either
no
-
load
mechanical
,
load
current
switching
,
bulk
capacitor
or
reactor
switching
operations
,
or
for
motor
starting
appli
-
cations
.
Vacuum
interrupters
,
as
used
on
the
15
VHK
circuit
break
-
ers
,
have
an
inherently
long
contact
life
and
will
provide
troublefree
service
under
varied
application
conditions
,
as
long
as
the
circuit
breaker
is
applied
within
its
rating
.
The
wear
condition
of
the
individual
vacuum
interrupters
will
vary
,
depending
on
circu
it
conditions
and
such
variables
as
single
phase
versus
three
-
phase
interruption
,
X
/
R
ratio
(
asymmetry
)
and
relay
delay
times
.
Of
course
,
interrupting
high
short
-
circuit
current
will
cause
contact
erosion
to
occur
faster
than
load
current
interruptions
.
The
interrupters
for
the
15
VHK
Circuit
Breakers
are
designed
and
tested
for
2000
%
KSI
minimum
.
It
is
unlikely
that
a
circuit
breaker
will
be
subjected
to
this
much
duty
during
the
life
of
the
breaker
D
.
C
.
Millivolt
Drop
Test
During
maintenance
periods
,
the
condition
of
the
breaker
current
circuit
can
easily
be
determined
by
performing
a
millivolt
drop
test
.
This
test
should
be
performed
regardless
of
whether
the
circuit
breaker
had
interrupted
low
or
high
currents
or
has
minimum
operations
.
The
following
table
lists
the
millivolt
drop
and
resistance
values
tor
the
circuit
breakers
covered
by
this
instruction
book
,
from
terminal
to
terminal
,
exclusive
of
the
primary
disconnects
.
Maximum
Maximum
MV
Drop
*
Micro
-
Ohms
Curcuit
Breaker
15
VHK
500
/
750
1
200
Ampere
7
35
;
15
VHK
500
/
750
2000
Ampere
6
30
Millivolt
drop
with
200
amperes
DC
flowing
.
Courtesy of NationalSwitchgear.com

Related product manuals