- 43 -
Minimum
level
Transmitter datum
Filling tee
Impulse lines filled
with stable liquid
Max level
Minimum level must be at
or above this datum
Application n° 2 : Liquid Level - Closed Tank Using a Flange-Mounted Transmitter
(No Condensable Vapors)
. . . ADDENDUM FOR FLANGE-MOUNTED TRANSMITTERS
Span = H1*G1, in inches w.g. if H1 is in inches
Lower range value = [H2*G1]-[H4*Gw], in inches w.g. if H2 and H4 are in inches
Upper range value = Lower range value + span
G1 = specific gravity of process liquid
Gw = specific gravity of liquid in wet leg
Transmitter datum
Minimum level must not
be below this datum
Max level
Minimum
level
Span = H1*G1, in inches w.g. if H1 is in inches
G1 = specific gravity of the process liquid
Lower range value = [H2*G1], in inches w.g. if H2 is in inches
Upper range value = Lower range value + span
Application n° 3 : Liquid Level - Closed Tank Using a Flange-Mounted Transmitter and a Wet Leg
(With Condensable Vapors)