Short-form Instruction Manual
for 266 pressure transmitters
Short-form Operating Instruction SOI/266-XC
Language Page
English.........................................................................................................................................................................1
Italian...........................................................................................................................................................................21
German........................................................................................................................................................................41
French...........................................................................................................................................................................61
TTG Activation.............................................................................................................................................................82
Declaration of conformity.............................................................................................................................................83
2600T Series Pressure Transmitters
Engineered solutions for all
applications

Questions and Answers

  • D
    David BrownAug 10, 2025
    What to do if ABB Transmitter detects an overpressure?
    • B
      bowerschristopherAug 10, 2025
      If the ABB Transmitter detects an overpressure because the measured process pressure value is outside the sensor limits and no longer represents the true applied process value, adjust the working range if possible.
  • F
    froyAug 15, 2025
    What to do if ABB Transmitter shows a pressure overrange?
    • K
      kwongAug 15, 2025
      If the ABB Transmitter indicates a pressure overrange because the measured static pressure is above its operational limit, adjust the working range if possible.
  • L
    Lisa ReyesAug 20, 2025
    How to execute replacement operation on ABB 266D after changing electronics or sensor?
    • K
      kimberly07Aug 20, 2025
      If the electronics or the sensor of your ABB Transmitter have been changed but the replacement operation has not been executed, you must perform the following steps: 1. Move the SW 1 of the electronics to position 1 to enable replace mode. 2. Select the SW 2 to indicate whether the new element is a new sensor or new electronics. 3. Power cycle the device. 4. Move the SW 1 of the electronics to position 0.
  • A
    Alicia RodriguezAug 26, 2025
    What to do if ABB 266D Transmitter sensor temperature is out of operational limits?
    • D
      Debra LamAug 26, 2025
      If the ABB Transmitter's measured sensor temperature is outside of its operational limits, check the valves and impulse line. If necessary, clean the impulse line and initiate PILD training.
  • N
    Natalie SmithAug 30, 2025
    What happens if ABB 266D device data is corrupted at start up?
    • M
      Mark RasmussenAug 30, 2025
      If the device data loaded at the start up of your ABB Transmitter are corrupted, precluding the correct functionality of the device because of exchange of data problems between Electronics and Sensor, the device will continue to work without problems, but at the next power cycle the new configuration will be lost.
  • K
    Kathryn NicholsSep 4, 2025
    Why is the electronic memory corrupted in my ABB Transmitter?
    • M
      Mary HaleySep 4, 2025
      If the electronic memory of your ABB Transmitter is corrupted due to a problem in the electronic circuit or in receiver circuit of the sensor, it means that writings to the electronic non-Volatile Memory was not successful.