4.2 Parameter list
Table 10: DNP 3.0 settings
Parameter Values (Range) Unit Step Default Description
DNP physical layer 1=Serial
2=TCP/IP
2=TCP/IP DNP physical layer
Unit address 1...65519 1 1 DNP unit address
Master address 1...65519 1 3 DNP master and UR address
Serial port 0=Not in use
1=COM 1
2=COM 2
0=Not in use COM port for serial interface, when physical layer
is serial.
Need time interval 0...65535 min 1 30 Period to set IIN need time bit
Time format 0=UTC
1=Local
1=Local UTC or local. Coordinate with master.
CROB select timeout 1...65535 sec 1 10 Control Relay Output Block select timeout
Data link confirm 0=Never
1=Only Multiframe
2=Always
0=Never Data link confirm mode
Data link confirm TO 100...65535 ms 1 3000 Data link confirm timeout
Data link retries 0...65535 1 3 Data link retries count
Data link Rx to Tx delay 0...255 ms 1 0 Turnaround transmission delay
Data link inter char delay 0...20 char 1 4 Inter character delay for incoming messages
App layer confirm 1=Disable
2=Enable
1=Disable Application layer confirm mode
App confirm TO 100...65535 ms 1 5000 Application layer confirm and UR timeout
App layer fragment 256...2048 byte
s
1 2048 Application layer fragment size
Legacy master SBO 1=Disable
2=Enable
1=Disable Legacy DNP Master SBO sequence number relax
enable
Default Var Obj 01 1...2 1 1 1=BI; 2=BI with status.
Default Var Obj 02 1...2 1 2 1=BI event; 2=BI event with time.
Default Var Obj 30 1...4 1 2 1=32 bit AI; 2=16 bit AI; 3=32 bit AI without flag;
4=16 bit AI without flag.
Default Var Obj 32 1...4 1 4 1=32 bit AI event; 2=16 bit AI event; 3=32 bit AI
event with time; 4=16 bit AI event with time.
1MRS756709 A Section 4
DNP 3.0 parameters
615 series 23