272 ACQ550-U1 User’s Manual
Technical data
Check that the operating time of the fuse is below 0.5 seconds. The operating
time depends on the fuse type, the supply network impedance as well as the cross-
sectional area, material and length of the supply cable. In case the 0.5 seconds
operating time is exceeded with the gG or T fuses, ultra rapid (aR) fuses will in most
cases reduce the operating time to an acceptable level.
Fuses, 208…240 V drives
Fuses, 380…480 V drives
ACQ550-x1-
see below
Input current
A
Input power (mains) fuses
IEC 60269 gG (A)
UL Class T (A) Bussmann type
-04A6-2 4.6 10
10 JJS-10
-06A6-2 6.6
-07A5-2 7.5
-012A-2 11.8 16
15 JJS-15
-017A-2 16.7 25
25 JJS-25
-024A-2 24.2
25 JJS-25
-031A-2 30.8 40
40 JJS-40
-046A-2 46.2 63
60 JJS-60
-059A-2 59.4
80 JJS-80
-075A-2 74.8 80
100 JJS-100
-088A-2 88.0 100
110 JJS-110
-114A-2 114 125
150 JJS-150
-143A-2 143 200
200 JJS-200
-178A-2 178 250
250 JJS-250
-221A-2 221 315
300 JJS-300
-248A-2 248
350 JJS-350
00467918.xls C
ACQ550-x1-
see below
Input current
A
Input power (mains) fuses
IEC 60269 gG (A)
UL Class T (A) Bussmann type
-03A3-4 3.3 10
10 JJS-10
-04A1-4 4.1
-06A9-4 6.9
-08A8-4 8.8 10
10 JJS-15
-012A-4 11.9 16
16 JJS-15
-015A-4 15.4 16
16 JJS-20
-023A-4 23 25
30 JJS-30
-031A-4 31 35
40 JJS-40
-038A-4 38 50
50 JJS-50
-045A-4 45
60 JJS-60
-059A-4 59 63
80 JJS-80
-072A-4 72 80
90 JJS-90
-078A-4 77
100 JJS-100
-097A-4 97 125
80 JJS-110