ACS 300 User’s Manual 83
Chapter 9 - Technical Data
Mains Connection
Motor Connection
1)
Check type-specific, refer to Table 1-1 and Table 1-2.
Voltage 1 and 3 phase
208 to 240 V
±10 %
1 and 3 phase
200 to 240 V
-7%
+10%
3 phase
380 to 480 V
±10 %
Frequency 48 to 63 Hz
Fundamental power factor approximately 0.98
Voltage 3 phase, 0 - U
MAINS
Frequency 0 to 500 Hz
Switching frequency f
s
1.0 to 16.0 kHz
Continuous load capacity,
constant torque at a maximum
ambient temperature of 50 °C
ACS 300 rated
current
see Figure 2-1
Overload capacity at a maximum
ambient temperature of
50 °C
Constant torque 1.5 * I
N
1 min every 10 min,
if switching frequency < 8 kHz
1)
Starting duty 1.5 * I
N
1 min every 10 min,
if switching frequency < 8 kHz
1)
Nominal motor voltage 200 to 240 V
360 to 500 V
Acceleration time 0.1 to 1800 s see page 48
Deceleration time 0.1 to 1800 s see Chapter 7 - Drive Parame-
ters