Chapter 2 – Installation and M/F Link Specification
ACS 600 Master/Follower Application Macro 2-3
Follower Fault
Information Wiring
The Follower does not send any feedback data via the serial Master/
Follower Link. Therefore it is highly recommended to separately wire
the Follower fault information back to the Master. The connection stops
both the Master drive and the Follower drives upon a Follower fault.
Figure 2-3 Follower fault information wiring. Note that the external input/output signals of ACS 601 and
ACS 604 units connect directly to the NIOC board I/O terminal blocks. On ACS 607, the I/O terminals
of the NIOC board are optionally wired to a separate terminal block (X2) at the factory.
ACS 60x
Follower
ACS 60x
Follower
ACS 60x
Master
X2
Relay Output 3
FAULT(-1)
Relay Output 3
FAULT(-1)
18 19 20
ACS 60x
Follower
ACS 60x
Follower
ACS 60x
Master
1 2 31 2 3 4 5 6 7 8 9
NIOC-xx Board
X27X22
+24 V d.c.
DI6: RUN ENABLE
1 2 3
Relay Output 3
FAULT(-1)
1 2 3 4 5 6 7 8 9
NIOC-xx Board
X27X22 1 2 3
Relay Output 3
FAULT(-1)
1 2 3 4 5 6 7 8 9
NIOC-xx Board
X27X22
ACS 601, ACS 604, ACS 607 without Terminal Block X2
30 31 32
+24 V d.c.
DI6: RUN ENABLE
X2
18 19 20 30 31 32
X2
18 19 20 30 31 32
ACS 607 with Terminal Block X2 (Optional)