EasyManua.ls Logo

ABB ACS 600 - Components Connected to Digital;Analogue Inputs; EMC

ABB ACS 600
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2 – Installation and M/F Link Specification
2-4 ACS 600 Master/Follower Application Macro
Master/Follower Link
Specification
Size of the Link: One Master and max. 10 Follower stations. If more
than 10 followers are required, an ABB representative should be
consulted.
Transmission medium: Fibre Optic Cable.
Construction: Plastic core, diameter 1 mm, sheathed with
plastic jacket
Attenuation: 0.23 dB/m
Maximum Length between Stations: 10 m
•Other:
Various lengths of fibre optic cables are available as optional add-on
kits for the ACS 600.
Connectors on the NAMC Board: Blue – receiver (HP 9534, T-1521);
grey – transmitter (HP 9534, R-2521)
Serial Communication Type: Synchronous, full Duplex
Transmission Rate: 4 Mbit/s
Transmission Interval: 4 ms
Maximum Transmission Delay: 16 ms
Protocol: Distributed Drives Communication System (DDCS)
Parameter Minimum Maximum Unit
Storage Temperature -55 +85 °C
Installation Temperature -20 +70 °C
Short Term Tensile Force 50 N
Short Term Bend Radius 25 mm
Long Term Bend Radius 35 mm
Long Term Tensile Load 1 N
Flexing 1000 cycles

Other manuals for ABB ACS 600