114 ACS2000 DFE UM 3BHS360367 ZAB E01 REV. K
5. Press the SUPPLY ON pushbutton on the con-
trol compartment door to close the MCB and
charge the DC link. The pushbutton lights up.
The status line of the CDP control panel alter-
nates between Charging and AuxiliaryOn.
After charging has finished, the state of the INU
changes to ReadyRun and the motor can be
started.
6. Enter the reference value.
For further information, see 9.9.2 Entering a
reference value.
7. Start the motor.
After the motor has been magnetized, the
motor speed ramps up to the reference value.
While the motor is accelerating, the run status
message on the display blinks. When the motor
speed has reached the reference value, the run
status message lights up permanently.
To indicate that the drive is operating, the dis-
play shows ReadyRef.
1 L ->
0.0 rpm
StateINU
Charging
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
0.0 rpm 0
StateINU
ReadyRun
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
[600.0 rpm] 0
StateINU
ReadyRun
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
600.0 rpm
StateINU
ReadyRef
MOTOR SP 0.00 rpm
POWER
1000.0 kW