CHAPTER 5 – MECHANICAL INSTALLATION 71
—
5.5 Installing fan units
The fans are always shipped separately from the drive.
Installation
1. Lift the fan unit onto the cabinet roof by means
of a forklift or a crane (if using a crane, employ
the lifting eyes in the fan roof).
Note: The mounting position can be identified by
the cutouts in the drive roof.
2. Use the supplied screws to fasten the fan unit
to the cabinet roof.
!
For information on the number of fan
units to be installed, see the applicable
mechanical drawings.
~73 kg
~94 kg
(fan units installed on
(fan units installed on
1MVA DFE drives)
2- 4MVA DFE drives)
!
For information on the electrical installa-
tion, see 6.11 Control and power supply
cables for fan units.
M8 25 Nm