98 ACS2000 DFE UM 3BHS360367 ZAB E01 REV. K
Mechanical installation
Electrical installation
1. Drive installed according to the instructions in the user manual
2. Drive securely fastened to the floor (if applicable)
3. Fan unit or fan units installed
4. Visual inspection:
no badly affixed or damaged components
no foreign objects inside cabinet
no dirt, dust and humidity inside cabinet
1. Types and cross-sections of control cables suitable for the signal type and signal level
2. Types and cross-sections of power cables selected according to the power cable specification
3. Pulse encoder cable screens connected to screen grounding point and not connected directly to the pulse
encoder interface (only applicable for drives with pulse encoder interface)
4. Cable entry prepared according to the instructions in the user manual
5. All control cable screens and conductors are connected according to the instructions of the user manual,
appropriately labelled, and the customer connections are completed
6. Heating cable (if supplied) installed according to the instructions in the user manual
7. Ground cable of drive securely connected at both ends
8. Input transformer and motor cables not connected at both ends (cables and drive must be meggered
before connection)