36 R5 Quick installation guide
See figure on page 37.
1. Install thin-wall conduit clamps for IP21/UL Type 1 or liquid-tight conduit connectors
for IP55/UL Type 12 (not supplied). Type 12 has a Pressfit gasket.
2. Connect conduit runs for input power, motor and control cables to the conduit box.
Ensure grommets (pointing down) are inserted into all unused holes.
3. Route the input power and motor wiring through separate conduits.
4. Strip wires.
5. Connect the motor and ground wires to the drive terminal. Tighten the screws to
torques shown in the Power wiring torque table.
6. Connect the input power and ground wires to the drive terminal. Tighten the screws
to torques shown in the Power wiring torque table.
7. Reinstall the shroud on the power
terminals by putting the tabs at the top
of the shroud in their counterparts on
the drive frame and then pressing the
shroud in place.
8. Route the control cables through the
conduit (not the same conduit as
either input power or motor wiring).
9. Strip the control cable sheathing and
twist the copper screen into a pig-tail.
10. Refer to page 38. Connect the ground
screen pig-tail for digital and analog
I/O cables. (Ground only at drive end.)
11. Connect the ground screen pig-tail for
Embedded fieldbus, EFB (EIA-485) cables at X5. (Ground only at drive end.)
12. Strip and connect the individual control wires to the drive terminals. Tighten the
screws to 0.4 lb-ft (0.5…0.6 N-m).