Safety instructions
9
Operation
These warnings are intended for all who plan the operation of the drive or operate 
the drive. 
WARNING! Ignoring the following instructions can cause physical injury or death, 
or damage to the equipment:
•
Before adjusting the drive and putting it into service, make sure that the motor 
and all driven equipment are suitable for operation throughout the speed range 
provided by the drive. The drive can be adjusted to operate the motor at 
speeds above and below the speed provided by connecting the motor directly 
to the power line. 
•
Do not activate automatic fault reset functions of the Standard Control Program 
if dangerous situations can occur. When activated, these functions will reset 
the drive and resume operation after a fault. 
•
Do not control the motor with the disconnecting device; instead, use the control 
panel keys   and  , or commands via the I/O board of the drive. The 
maximum allowed number of charging cycles of the DC capacitors (i.e. power-
ups by applying power) is five in ten minutes.
Note: 
•
If an external source for start command is selected and it is ON, the drive (with 
Standard Control Program) will start immediately after fault reset unless the 
drive is configured for 3-wire (a pulse) start/stop.
•
When the control location is not set to Local (L not shown in the status row of 
the display), the stop key on the control panel will not stop the drive. To stop 
the drive using the control panel, press the LOC/REM key and then the stop 
key .