Safety pulse encoder parameters
The drive parameter settings in ACS880 primary control program when you use a pulse
encoder:
parameter 90.41 Motor feedback selection is set to value Encoder 1.
parameter 90.45 Motor feedback fault is set to value Warning.
Note: If you want that the drive trips on encoder faults, set this parameter to value Fault.
For more information, see the firmware manual.
parameter 92.21 Encoder cable fault mode is set to value A, B, Z.
SS1 ramp parameters
You must set these parameters only for the Emergency stop, stop category 1 option. If FSO
parameter 200.112 SAR1 ramp time to zero is set to 0, drive parameters define the stop
ramp that is used in the SS1 function (stop category 1):
21.04 Emergency stop mode is set to value Eme ramp stop (Off3)
23.23 Emergency stop time is set to a suitable value.
Also in this case, the FSO module monitors the actual stop ramp (ramp monitoring or time
monitoring).
For more information, see the firmware manual.