Action
Turn the emergency stop button [S61] until it releases and returns to the up position.
Push the emergency stop reset button [S62]. Make sure that:
the emergency stop reset button indicator light [S62] goes off.
the main contactor/breaker closes.
the drive does not restart automatically at this point.
Power up the drive:
If the drive tripped on a fault, reset the faults from the drive
Make sure that the operating switch is set to ON (1)
Switch on the drive start signal.
For more information, see the hardware manual.
Restart the drive and make sure that the drive and the motor operate normally.
Repeat the test from each operating location (for every emergency stop button and reset button).
Fill in and sign the acceptance test report which verifies that the safety function is safe and accepted
for operation.