Program features 91
Miscellaneous
User parameter sets
The drive supports four user parameter sets that can be saved to the permanent
memory and recalled using drive parameters. It is also possible to use digital inputs to
switch between user parameter sets.
A user parameter set contains all editable values in parameter groups 10…99 except
forced I/O values such as parameters 10.03 DI force selection and 10.04 DI force
data
I/O extension module settings (groups 14…16)
fieldbus communication enable parameters (50.01 FBA A enable and 50.31 FBA
B enable)
other fieldbus communication settings (groups 51…56 and 58)
encoder configuration settings (groups 92…93),
some hardware settings in parameter group 95 HW configuration, and
user set selection parameters 96.1196.13.
As the motor settings are included in the user parameter sets, make sure the settings
correspond to the motor used in the application before recalling a user set. In an
application where different motors are used with the drive, the motor ID run needs to
be performed with each motor and the results saved to different user sets. The
appropriate set can then be recalled when the motor is switched.
If no parameter sets have been saved, attempting to load a set will create all sets
from the currently active parameter settings.
Switching between user parameter sets is only possible with the drive stopped.
Settings
Parameters 96.1096.13 (page 421).
Parameter checksum calculation
A parameter checksum can be calculated from a user-definable set of parameters to
monitor changes in the drive configuration. The calculated checksum is compared to
1…4 reference checksums; in case of a mismatch, an event (a pure event, warning or
fault) is generated.

Table of Contents

Other manuals for ABB ACS880 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 Series and is the answer not in the manual?

ABB ACS880 Series Specifications

General IconGeneral
Cooling MethodAir-cooled, liquid-cooled
Enclosure classIP21, IP55
Mounting typeWall-mounted
Control methodDirect torque control (DTC)
Braking chopperIntegrated or external
CommunicationEthernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overload, short circuit, overtemperature, earth fault
Operating Temperature Range-15°C to +50°C
Storage Temperature Range-40°C to +70°C
Relative Humidity5 ... 95 % (non-condensing)
Safety featuresSafe torque off (STO)

Related product manuals