AquaMaster 3
Electromagnetic flowmeter
MODBUS Tables Supplement COI/FET2XX/MOD/TBL-EN 10
MODBUS Protocol
1.3.8 RW String
Read/Write access to string types.
Each AquaMaster 3 String type requires 18 MODBUS Registers (36 bytes). Consequently, RW String
Register addresses are assigned at intervals of 18 and the Request Message must provide Quantity of
Registers in multiples of 18.
Read Holding Registers 10217 to 10234
var163 Owner string
Request Message
(Hex)
Response Message
(Hex)
=char
Error Message
(Hex)
Address
01
Address
01
Function
83
Function
03
Function
03
Exception Code
Exception Code
Starting Address Hi
27
Byte count
24
Starting Address Lo
e8
byte0
41
A
Quantity of Registers Hi
00
byte1
42
B
Quantity of Registers Lo
12
byte2
42
B
CRC
4f
byte3
20
space
CRC
47
byte4
53
S
byte5
74
t
byte6
6f
o
byte7
6e
n
byte8
65
e
byte9
68
h
byte10
6f
o
byte11
75
u
byte12
73
s
byte13
65
e
byte14
00
null
byte15
00
byte16
00
byte17
00
byte18
00
byte19
00
byte20
00
byte21
00
byte22
00
byte23
00
byte24
00
byte25
00
byte26
00
byte27
00
byte28
00
byte29
00
byte30
00
byte31
00
byte32
00
byte33
00
byte34
00
byte35
00
CRC
a9
CRC
b8

Other manuals for ABB AquaMaster 3

Related product manuals