AquaMaster 3
Electromagnetic flowmeter
MODBUS Tables Supplement COI/FET2XX/MOD/TBL-EN 19
MODBUS Protocol
RW 8/16Bit
Address
AquaMaster 3
Parameter
Name
Size
(bytes)
Range/Units
MID
?
Note
8001
026
UserFlowSensorZero
2
0.01 mms
—1
y
User's flow sensor zero
correction
8002
037
TotaliserUnits
1
0 to 6
y
See Note 1
8003
040
TariffMode
1
0 to 7
y
See Note 1
8004
041
TariffUnits
1
1 to 6
y
See Note 1
8005
044
TariffWeeklyCycleStartDay
1
0 to 7
y
See Note 1
8006
045
TariffWeeklyCycleEndDay
1
0 to 7
y
See Note 1
8007
048
ABB Reserved
1
y
8008
067
PulseOutputUnits
1
0 to 6
See Note 1
8009
069
PulseMaximumFrequency
2
0 to 50 Hz
8010
070
FunctionOfOutput1
1
0 to 3
See Note 1
8011
071
FunctionOfOutput2
1
0 to 4
See Note 1
8012
072
FunctionOfOutput3
1
0 to 3
See Note 1
8013
102
FlowmeterMode
1
0 to 3
y
0 = Normal, 1 = Backwards,
2 = Fwd Only, 3 = Rev Only
8014
109
VelocityUnits
1
0 to 8
See Table A.5 Velocity Units
8015
112
FlowUnits
1
0 to 19
See Note 1
8016
117
FlowCutOffLow
1
0 to 255 mms
—1
y
Factory flow cut off
(battery mode)
8017
118
UserFlowCutOff
1
0 to 255 %
y
User's flow cut off setting
8018
119
PressureUnits
1
0 to 7
See Note 1
8019
125
TripPointForHFlow
2
200 to +200 %
8020
126
TripPointForLFlow
2
200 to +200 %
8021
131
HysteresisForFlowTrip
1
0 to 10 %
8022
140
EmptyPipeTripLevel
2
0 to 999.9 kOhm
8023
141
ABB Reserved
1
8024
142
ABB Reserved
1
8025
143
ABB Reserved
1
8026
144
ABB Reserved
1
8027
145
ABB Reserved
1
8028
150
ABB Reserved
2
y
8029
158
PowerControlMode
1
0 to 60 s
Measurement rate
(battery mode)
8030
159
DateFormat
1
0 to 2
See Table A.4 Date Format
8031
160
DisplayTimeout
1
0 to 255 mins
0=1min
8032
161
Language
1
0 to 6
0 = ??, 1 = UK, 2 = F,
3 = NL, 4 = DE, 5 = I,
6 = E
8033
164
PressureLoggerFormat
1
0 to 1
0 = Off, 1 = mBar Abs
8034
165
FlowLoggerFormat
1
0 to 1
0 = Off, 1 = mms
—1
8035
166
MainLoggerInterval
2
1 to 65535 mins
8036
167
ABB Reserved
1
8037
168
ABB Reserved
2
8038
170
ABB Reserved
1
8039
176
PressureType
1
0 to 1
Transducer type
0 = Gauge, 1 = Absolute
8040
177
ABB Reserved
1
1
Refer to AquaMaster 3 Programming Guide COI/FET2XXEN for settings.