AquaMaster 3
Electromagnetic flowmeter
MODBUS Tables Supplement COI/FET2XX/MOD/TBL-EN 3
1.2 AquaMaster 3 MODBUS Register Mapping
The AquaMaster 3 MODBUS interface provides access to AquaMaster 3 parameters described in the
AquaMaster 3 Programming Guide (part no. COI/AQUAMASTER3-EN).
In general, AquaMaster 3 parameters with security access levels 0 to 7 can be read via MODBUS and,
where defined, parameters with security access levels 0 to 4 can be written via MODBUS.
Writeable parameters identified as MID parameters (see Appendix A) become Read Only via MODBUS if
the AquaMaster 3 flow meter has been configured for use as an MID instrument – refer to the
AquaMaster 3 Programming Guide (COI/AQUAMASTER3-EN) for details. Attempting to write to MID
parameters in an MID instrument results in MODBUS exception code 04, Slave Device Failure.
Table 2.1 shows the mapping of AquaMaster 3 MODBUS Registers to MODBUS Function Codes and
AquaMaster 3 data types, section 1.3 provides details of usage for each Register Address Range and
Appendix A provides the Register allocation tables.
Applicable Function
Codes
01 Read Coils
05 Write Single Coil
15 Write Multiple Coils
Read/write access to single bit types.
Read only access to single bit types.
Read only access to 8- and 16-bit types.
Read only access to string types.
Read only access to 32-bit types.
Read only access to float types.
03 Read Holding Registers
06 Write Single Register
16 Write Multiple Registers
Read/write access to 8- and 16-bit types.
03 Read Holding Registers
16 Write Multiple Registers
Read/write access to string types.
03 Read Holding Registers
16 Write Multiple Registers
Read/write access to 32-bit types.
03 Read Holding Registers
16 Write Multiple Registers
Read/write access to float types.
Table 2.1 AquaMaster 3 MODBUS Register Mapping