Connector data
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5
… 2.5 mm
2
(22…12 AWG). Connector pitch is 5 mm.
The maximum tightening torque for screw terminals is 0.45 N·m (4 lbf·in).
24 V DC (±10%), 2 APower supply (XPOW)
External power input.
Two supplies can be connected to the BCU control unit for
redundancy.
250 V AC / 30 V DC, 2 ARelay outputs RO1…RO3
(XRO1…XRO3)
Protected by varistors
Total load capacity of these outputs is 4.8 W (200 mA / 24 V)
minus the power taken by DIO1 and DIO2.
+24 V output (XD24:5 and XD24:7)
24 V logic levels: “0” < 5 V, “1” > 15 VDigital inputs DI1…DI6
(XDI:1…XDI:6)
R
in
: 2.0 kohm (DI1…DI5)
Input type: NPN/PNP (DI1…DI5), PNP (DI6)
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
I
max
: 15 mA (DI1…DI5), 5 mA (DI6)
24 V logic levels: "0" < 5 V, "1" > 15 VStart interlock input DIIL (XDI:7)
R
in
: 2.0 kohm
Input type: NPN/PNP
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
6