EasyManua.ls Logo

ABB CIRCUIT SHIELD 87T - Page 15

ABB CIRCUIT SHIELD 87T
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Transformer
Differential
Relay
IB
7.6
.
1.7
-
4
Page
15
3
.
BUILT
-
IN
TEST
FUNCTION
A
built
-
in
test
function
is
provided
for
convenience
in
running
a
test
on
the
relay
and
associated
trip
circuits
.
The
test
button
is
labelled
TRIP
,
and
depressing
the
button
will
cause
an
immediate
trip
.
tests
should
be
made
with
the
main
circuit
de
-
energized
.
If
tests
must
be
CAUTION
:
made
on
an
energized
circuit
,
take
all
necessary
precautions
.
4
.
ACCEPTANCE
TESTS
and
adjust
the
operating
characteris
-
The
following
procedures
can
be
used
to
verify
tics
of
the
Type
87
T
relay
.
A
.
Minimum
Operating
Current
and
%
Differential
Tests
:
Connect
the
relay
in
the
test
circuit
shown
in
Figure
8
.
Apply
control
voltage
per
the
relay
s
rating
as
marked
on
the
front
panel
.
Select
and
make
settings
from
the
listing
in
Table
5
.
Minimum
Operating
Current
:
Increase
the
I
2
current
until
the
87
T
operates
.
(
11
=
0
)
Compare
with
the
expected
value
from
Table
5
.
Pifferential
Characteristic
:
Set
the
I
2
current
for
5.8
amps
.
Increase
the
I
1
current
to
5.8
amps
.
The
87
T
output
contact
should
now
be
open
.
Reset
the
target
to
black
.
Increase
the
I
1
current
until
the
87
T
operates
.
The
I
1
current
should
be
within
the
limits
shown
.
Remember
:
since
the
%
Differential
and
Minimum
Restraint
dials
are
continuously
adjustable
,
you
may
trim
their
positions
if
desired
to
obtain
more
precisely
the
required
operating
values
.
Important
note
:
Some
commercial
test
sets
that
have
2
independent
sources
are
not
suitable
for
the
differential
test
shown
above
because
there
is
a
phase
-
shift
between
the
sources
.
If
you
are
using
such
a
set
,
then
an
alternative
test
for
the
differential
element
using
a
single
source
is
as
follows
:
a
.
Connect
the
relay
as
shown
in
Figure
9
.
b
.
Set
%
Diff
dial
to
40
%
,
taps
to
3.6
A
.
c
.
Apply
7.2
A
test
current
.
The
relay
should
not
trip
.
d
.
Move
one
tap
pin
to
2.9
A
position
.
Apply
7.2
A
and
then
rotate
the
%
Diff
dial
counterclockwise
slowly
until
the
relay
trips
.
The
dial
position
should
be
21
-
27
%
.
Suggested
Settings
for
the
Acceptance
Test
Table
5
:
(
D
)
(
R
)
Min
Restraint
Min
Operate
Lim
Differential
Test
Set
I
2
I
1
limits
I
2
%
Diff
Taps
2.9
A
2.9
A
2.9
A
1 5
%
2.3
0.75
0.75
0.75
1.0
A
1
.
0
A
1.0
A
5.8
A
5.8
A
5.8
A
6.4
6.9
A
7.5
A
8.4
A
25
%
1
.
5
7.0
40
%
1
.
0
7.8
The
suggested
settings
selected
for
Table
5
use
the
lowest
tap
value
(
2.9
A
)
to
minimize
the
currents
required
for
the
tests
.
If
you
must
check
the
values
to
be
used
in
your
application
,
the
following
formulas
apply
:
1
.
Minimum
operating
current
:
Im
D
=
%
Diff
setting
,
R
=
Minimum
Restraint
Setting
Increase
the
test
current
to
one
input
of
the
relay
.
The
relay
should
trip
within
+
/
-
15
%
of
the
value
calculated
.
(
Trim
dial
position
as
rqd
.
)
(
D
/
(
100
+
D
)
x
R
x
T
tap
value
T
2
.
Differential
characteristic
:
apply
test
currents
of
2
times
the
tap
value
to
each
of
two
current
inputs
.
The
output
contact
should
be
open
.
Increase
one
source
until
the
output
contact
closes
.
The
current
at
which
the
contact
closes
should
be
within
+
/
-
5
%
of
the
value
calculated
from
:
1
=
T
x
(
2
D
+
2
)
T
=
tap
of
"
increased
D
=
%
Diff
setting
.
source
Courtesy of NationalSwitchgear.com

Related product manuals