EasyManua.ls Logo

ABB CIRCUIT SHIELD 87T - Page 3

ABB CIRCUIT SHIELD 87T
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Transformer
Differential
Relay
IB
7.6
.
1.7
-
4
Page
3
Connections
:
Typical
connection
diagrams
for
two
and
three
Internal
connections
in
Figure
2
.
winding
transformers
are
shown
in
Figures
3
and
4
.
Special
care
should
be
taken
to
connect
the
dc
control
power
in
the
proper
polarity
.
These
relays
have
a
metal
front
panel
which
is
connected
through
printed
circuit
board
runs
to
a
rear
terminal
marked
"
G
"
.
In
all
applications
this
terminal
should
be
wired
to
ground
.
The
87
T
relay
includes
an
external
resistor
which
is
supplied
mounted
to
the
case
and
wired
between
terminals
9
and
operation
.
This
resistor
must
be
connected
for
proper
10
.
Note
:
Connections
are
critical
in
this
application
.
Most
problems
experienced
during
commissioning
are
due
to
incorrect
connections
:
interchanged
phases
,
or
ct
polari
-
ties
,
or
incorrect
make
-
up
of
the
delta
ct
connections
.
Using
the
transformer
nameplate
drawing
as
the
reference
,
a
phasing
-
check
should
be
made
to
be
sure
that
the
ct
secondary
connections
are
made
up
properly
properly
for
the
particular
transformer
winding
configuration
.
In
case
of
difficulty
during
commissioning
,
a
plug
-
in
test
unit
is
available
on
loan
from
the
factory
as
an
aid
in
analyzing
connection
problems
;
however
,
significant
load
current
must
be
flowing
to
use
this
device
.
3
.
SETTINGS
Procedures
for
calculating
settings
for
a
particular
installation
are
given
in
the
Application
section
.
CURRENT
TAPS
:
The
ct
secondary
currents
seen
by
the
relay
are
usually
unequal
due
to
the
primary
to
secondary
ct
s
on
the
primary
and
secondary
sides
of
the
transformer
.
ratio
of
the
transformer
being
protected
and
the
choice
of
ratios
for
the
The
tap
settings
are
selected
to
equalize
the
input
currents
seen
by
the
differ
-
ential
measurement
unit
of
the
relay
.
The
tap
values
and
ratios
provided
are
shown
in
Table
1
.
Setting
calculations
will
determine
the
tap
selection
required
for
the
high
-
side
and
low
-
side
ct
inputs
.
It
is
important
to
identify
which
input
terminals
of
the
relay
are
connected
to
the
high
-
side
ct
s
and
to
the
low
side
ct
s
.
these
Then
when
making
settings
,
to
relate
the
front
panel
tap
to
the
input
current
terminals
it
affects
:
the
left
side
tap
for
input
terminals
1
-
2
,
the
right
side
tap
for
terminals
5
-
6
,
and
the
center
tap
(
on
3
winding
units
)
for
input
terminals
3
-
4
.
%
DIFFERENTIAL
:
The
ABB
Circuit
-
Shield
Type
87
T
relay
operates
when
its
input
currents
differ
in
magnitude
(
vectorial
1
y
)
.
The
operating
point
occurs
when
the
difference
,
expressed
as
a
percentage
of
the
smaller
,
exceeds
the
setting
.
The
percentage
differential
or
"
slope
"
setting
is
made
with
the
left
-
hand
front
panel
dial
.
illustrated
in
the
graphs
of
Figures
6
and
7
.
the
operate
current
relative
to
the
tap
value
,
This
continuously
adjustable
control
allows
settings
from
15
to
40
%
,
and
is
In
these
plots
the
vertical
axis
is
Mo
=
(
Ii
/
T
1
)
-
(
I
2
/
T
2
)
and
the
horizontal
axis
is
the
smaller
restraint
current
relative
to
tap
value
MR
=
I
2
/
T
2
The
Percent
Differential
is
D
=
MO
/
MR
where
i
nto
and
i
nto
11
is
the
1
arger
restraint
current
T
1
the
tap
value
,
12
is
the
smaller
restraint
current
T
2
the
tap
value
.
Note
:
MR
=
R
when
I
2
/
T
2
<
R
where
R
(
adjustable
)
Minimum
Restraint
Courtesy of NationalSwitchgear.com

Related product manuals