27
TRANSFORMER COMPONENTS
Register
address
Operations Description Notes
Operation for controlling
0x300 R / W CH1 Alarm Setting
[°C]
0x301 R / W CH2 Alarm Setting
[°C]
0x302 R / W CH3 Alarm Setting
[°C]
0x303 R / W CH4 Alarm Setting
[°C]
0x310 R / W CH1 Trip Setting
[°C]
0x311 R / W CH2 Trip Setting
[°C]
0x312 R / W CH3 Trip Setting
[°C]
0x313 R / W CH4 Trip Setting
[°C]
0x272 R / W Fan OFF
Temperature
Setting [°C]
0x273 R / W Fan ON
Temperature
Setting [°C]
0x27F W Reset Maximum
Temperature
W r i t e 0 x A 5 5 A t o r e s e t
Unsigned int
Real Value = Read Value (dec) - 25