CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E 67
AssetVision Basic with the ABB CoriolisMaster Device Type
Manager (DTM)
The required software and drivers can be downloaded
using the adjacent download link.
Installation of the software and connection to the flowmeter:
1. Unpack the downloaded archive file to the c:\temp folder.
2. AssetVision Basic (DAT200) install
‘3KXD151200S0050_Tool_DAT200_Asset_Vision_Basic’.
3. HART Communication DTM install
‘CWCommDTMHART_1.0.55’.
4. CoriolisMaster DTM FCXxxx install
"3KXF410100S0002_DTM_FCXxxx_HART_CoriolisMaster‘.
5. Connect the flowmeter with the PC / laptop, see chapter
Parameterization via the infrared service port adapter on
page 69 or Parameterization via HART® on page 69.
6. Power-up the power supply for the flowmeter and start
AssetVision Basic on the PC / laptop
Select HART and ‘HART Communication Version 1.0.52’.
Select ‘Extended HART modem’.
Select the corresponding COM port.
Activate the ‘Multimaster and Burst mode support’
option.
The flowmeter is detected and the CoriolisMaster DTM
starts automatically.
Confirm the dialog field ‘Upload parameters’ by selecting
‘yes’.
COM settings
Baud rate 19200
Number of Stop bits 1
RTS Control Toggle
DTR Control Enable
Parity Odd
Master Primary Master
Preamble 5
Number of communication retries 3
Start Address 0
End Address 0
Communication timeout 10 s