Procedure • Record the current Level Value before the mounting
change.
• Change the mounting from Top to Bottom or vicer
versa.
• Change the Signal Polarity in the Diagnostic Menu
(typically Standard for bottom mount and Reversed
for top mount)
• If the points were just swapped and kept in the
versa), the level indicated might deviate between
mounting orientation but if the the points were
physically displaced up or down the deviation might
be larger.
• Calculate the deviation of the level reading between
previous and new mounting.
• There are two ways to handle this:
add the determined deviation
- Apply Offset. Notice that when the Offset is
used it leaves behind the LRV & URV, which need
to be set again.
• End