COPA-XE / MAG-XE
Instruction Bulletin
Electromagnetic Flowmeter
with Pulsed DC Magnetic
Field Excitation
Model DE41.. / DE43..
DE21.. / DE23..
Valid for Software Versions B.11 and higher
D184B105U02 Rev. 01 / 05.2000
ABB Automation

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the ABB MAG-XE and is the answer not in the manual?

ABB MAG-XE Specifications

General IconGeneral
Model SeriesMAG-XE
Housing MaterialAluminum, Stainless Steel
Process Temperature-40°C to +180°C
Process PressureUp to 40 MPa (5800 psi) depending on flange rating and lining
Power Supply100 to 230 V AC, 24 V AC/DC
Output Signal4 to 20 mA, frequency, pulse, status
CommunicationHART, FOUNDATION Fieldbus, PROFIBUS PA/DP
Lining MaterialPTFE, PFA
Electrode MaterialStainless Steel, Hastelloy, Tantalum, Titanium
Protection ClassIP67, IP68
Temperature Range-40°C to +60°C (ambient)

Summary

Introductory Safety Notes

Regulated Usage

Defines intended applications and user responsibilities for EMF systems.

Flowmeter Primary and Converter Coordination

Compact Design COPA-XE

Describes the integrated mechanical design of the COPA-XE flowmeter.

Remote Design MAG-XE

Explains the remote mounting capabilities of the MAG-XE flowmeter system.

Principle of Operation

Explains the fundamental operating principle of electromagnetic flowmeters.

Measurement Principle

Details the application of Faraday's Law of Induction for flow measurement.

Assembly and Installation

Flowmeter Primary Installation Requirements

Details site requirements and installation guidelines for the flowmeter primary.

Flowmeter Primary Installation

Covers installation procedures, gasket surfaces, protection plates, and torque specifications.

Programming the Converter

Data Entry

Describes how to enter data using the magnet stick and keypad.

Parameter Overview and Data Entry

Presents a detailed overview of parameters and their entry methods.

Parameter Entry

Program Protection

Explains how to enable and disable parameter protection.

Qmax

Setting the flow range end value for both forward and reverse flow directions.

System Zero

Details procedures for adjusting the zero point of the flowmeter.

Setting the MAX-Alarm

Configures the upper limit for flow rate alarms.

Submenu Data Link

Manages communication protocols like Profibus, HART, and ASCII.

Submenu Function Test

Provides functions to test instrument components independently of flow.

Submenu "Empty Pipe Detector"

Details settings for the optional empty pipe detection feature.

Error Message

Accuracy

Safety Relevant Section

Grounding the Flowmeter Primary

Provides essential grounding procedures for safety and EMC compliance.

Signal and Excitation Cable Connections

Details cable connections for signal and excitation for MAG-XE models.

Interconnection Diagrams

Safety Information

Contains critical safety notes for working with the instrument.

Start-Up

Initial Checks

Outlines pre-start-up checks for both COPA-XE and MAG-XE models.

Related product manuals