In-/ Output connection on MControl front
Input
(optical isolated, one common)
Output
(two outputs share one
common)
II II Over voltage class
3 3 Pollution severity
24 VDC 250 VAC 50/60 Hz Nominal voltage
0.33 kV 2.5 kV Impulse voltage withstand level
10 mA (16mA) 1 A Nominal current (cosphi 0.4)
1.5 mm
2
1.5 mm
2
Nominal cross-section of connector
5 * 10
6
mechanical
3 * 10
4
electrical
Minimum operations
230V AC 230 VDC 24 VDC Max switching voltage
1 A 150 mA 6 A Max switching current
500 VA Max switching capacity
7