Electrical installation
Modbus Connection
Connect Modbus to X3.
General
Arrange the communication cables as far away from the motor cables as possible. Avoid parallel runs. Use bushings at cable
entries.
—
Connector X3
PIN Description
GND. Isolated signal ground
Data A (inverting)
Bus termination
equipped with internal bus termination
devices located at bus ends.
Communication settings
communication / Modbus RTU) and are copied then automatically to the MRP31.0. After changing communication settings
perform a power cycle.
Master supervision
busfault reaction.
Modbus bus timeout
Default 0 ms (deactivated)
Supported baudrates
Modbus data frame
•
•
•
•
Slave address
bus address.
8 UNIVERSAL MOTOR CONTROLLER UMC100.3 | MRP31.0 MODBUS TCP COMMUNICATION MODULE MANUAL