5
5
Manual
motor protectors
Low Voltage Products & Systems 5.7
ABB Inc. • 888-385-1221 • www.abb-control.com AC 1000 - 11/03
Type MS116
Technical data
General purpose
MS116 range Maximum current (600 VAC Max.)
0.1 – 0.16 0.16
0.16 – 0.25 0.25
0.25 – 0.40 0.40
0.04 – 0.63 0.63
0.63 – 1.0 1.0
1.0 – 1.6 1.6
1.6 – 2.5 2.5
2.5 – 4.0 4.0
4 – 6.3 6.3
6.3 – 10 10
8 – 12 12
10 – 16 16
Maximum ratings
Horsepower, HP, Breaking-All-Lines
MS116 Single phase Three phase
Range 50/60 Hz 50/60 Hz
120 VAC 240 VAC 240 VAC 480 VAC 600 VAC
0.1 – 0.16 — — — — —
0.16 – 0.25 — — — — —
0.25 – 0.40 — — — — —
0.40 – 0.63 — — — — —
0.63 – 1.0 — — — 1/2 1/2
1.0 – 1.6 — 1/10 — 3/4 3/4
1.6 – 2.5 — 1/6 1/2 1 1 1/2
2.5 – 4.0 1/8 1/3 1 2 3
4.0 – 6.3 1/4 1/2 1 1/2 3 5
6.3 – 10 1/2 1 1/2 3 5 7 1/2
8 – 12 1/2 2 3 7 1/2 10
10 – 16 1 2 5 10 10
Short circuit ratings
18,000 RMS symmetrical 480 VAC
5,000 RMS symmetrical 600 VAC