42
Others
Decimal Read Write Variable Data type Comment
hexadecimal hexadecimal name
802 0x0322 0xFCDE .PG_SCHNELL INT Fast forward/backward
804 0x0324 0xFCDC .PG_SEG INT Segment number of active program
1047 0x0417 0xFBE9 .PG_SEGZEIT DINT Run time in segment of PS
1053 0x041D 0xFBE3 .PG_ZYKLEN INT Processed loops of PS
1799 0x0707 0xF8F9 .POS_WW BOOL IND-Loop indicates effective setpoint
1800 0x0708 0xF8F8 .POS_Y BOOL IND-Loop indicates output value
1817 0x0719 0xF8E7 .PRG_BA1 BOOL Binary track 1 of program source
1818 0x071A 0xF8E6 .PRG_BA2 BOOL Binary track 2 of setpoint generator
1819 0x071B 0xF8E5 .PRG_BA3 BOOL Binary track 3 of setpoint generator
1820 0x071C 0xF8E4 .PRG_BA4 BOOL Binary track 4 of setpoint generator
1816 0x0718 0xF8E8 .PRG_ENDE BOOL Active program terminated
1801 0x0709 0xF8F7 .REMOTE BOOL Remote control of controller via RS-232/485
1039 0x040F 0xFBF1 .RTC_DATUM DINT Date and time [s]
1055 0x041F 0xFBE1 .RTC_ERROR INT Clock error
1054 0x041E 0xFBE2 .RTC_STATUS INT Clock state
1041 0x0411 0xFBEF .RTC_ZEIT DINT Time [msec]
1809 0x711 0xF8EF .SETZ_DATUM BOOL Set time
1791 0x06FF 0xF901 .STEPS_B BOOL IND-loop backwards
1792 0x0700 0xF900 .STEPS_F BOOL IND-loop forwards
1794 0x0702 0xF8FE .STEPW_F BOOL SP-W-loop forwards
751 0x02EF 0xFD11 .TAB01 REAL Output table 1
753 0x02F1 0xFD0F .TAB02 REAL Output table 2
755 0x02F3 0xFD0D .TAB03 REAL Output table 3
757 0x02F5 0xFD0B .TAB04 REAL Output table 4
807 0x0327 0xFCD9 .W_P REAL Ramp setpoint of setpoint generator
1813 0x0715 0xF8EB .WW_UM BOOL
771 0x0303 0xFCFD .ZK01 REAL Output status correction 1
773 0x0305 0xFCFB .ZK02 REAL Output status correction 2
901 0x0385 0xFC7B Tastatur INT Keyboard remote control