5:3.3.2 Downloading parameters
To download the parameters, connect the keypad to the chosen softstarter and select To Starter. A text
Load to Start will be displayed. Continue by pressing Execute and then Yes when the text Are You Sure is
displayed. Transfer OK will now be displayed if the transmission was successful; otherwise, Transfer Not OK
will be displayed. Set the parameter Setting le and conrm by pressing Next.
Information!
The parameters in the menu Service Settings will not be transferred.
To learn how to operate the keypad, see Chapter 6 “Human-Machine Interface (HMI)”
5:3.3.3 Technical data
Chapter 5
Connection
1L1
2T1
4T2
6T3
B1
B2
B3
3L2
5L3
1
100-250V
Stop
Start
In0
In1
Vc
AC/DC, 50/60 Hz
2
3
4
5
6
7
8
9
10
Vp
Vp
11
K4
12
13
14
Vn
15
16
K5
17
18
19
K6
20
LISTED 7F39
IND. CONT. EQ
.
1SFA 894 007
IEC 947-4-2
Ie: 37-72A
Us: 100-250V A
C/DC
UL
Uc: 100-250V A
C/DC
FLA: 37-68A
Made in Sweden
Ue: 220-23
0 380-400 50
0 V
72: AC-53a: 8-1.6:
In line 18,5
37
45 kW
Ue 2
08 220-240 44
0-480 V
PTC
Key-Pad
FELDBUSS
CAUTION
Fuse 250A TYP
OWER ZILOX
Max short circuit
current 65kA at
Wire 1-8 Al Cu
75C only, 35lb-in
Overload Capacity
115% of Conti
nuous
L
N
Figure 30: Download
Display LCD type
Signal indication LEDs Power on: Green
Protection: Yellow
Fault: Red
Ambient temperature Storage: -25°C to +70°C (-13°F to 158°F)
Operation: 0°C to +50°C (32°F to 122°F)
Degree of protection IP66
UL approval Type 1
Type 4X Indoor
Type 12
Marine approvals Contact your ABB sales ofce
Low Voltage Products & Systems 5.9
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 021 M0201