42 Connection | Installation and commissioning manual | 1SFC132081M0201
External control voltage
You can control the Softstarter with an external 24 V DC
source from a PLC or similar, if necessary.
Connect the cables. See Figure 5.9 to use the internal
holding circuit, or Figure 5.10 to use an external holding
circuit.
WARNING
Use only 24 V DC to connect terminal 13, 14,
15, 16 and 17. Other voltages can damage the
Softstarter and the warranty will no longer be
valid.
Tightening torques and cable dimensions.
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
AWG 12 ... 24
0,5 Nm
4,3 lb.in
3,5 x 0,6 mm
(0.138 x 0.024 in)
M3
L
100-250V
50/60 Hz K4 K5 K6
Stop In0 In1 In2 GND +24V
N
1SFC132081M0201
Figure 5.9
Holding circuit with external control voltage
(pulse for start is enough)
PSTX
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In1 In2 DGND +24V
N
DC
+ -
1SFC132081M0201
In0 GND
Figure 5.10
Conventional circuit with external control voltage
(maintained start signal is required)
PSTX
L
100-250V
50/60 Hz K4 K5 K6
Start Stop In1 In2 DGND +24V
N
STOP
START
N
DC
+ -
1SFC132081M0201
In0
GND
5