110 Functions | Installation and commissioning manual | 1SFC132081M0201
7.17.18 Too long start time protection
Too long start time protection
Too long start time protection has these parameters:
Parameter Description Setting range Default value
18.11 Too long start trip time Trip time in seconds. 1.0 ... 500.0 s 500.0 s
18.12 Too long start out Specifies the Event groups this
protection belongs to.
Eventgroup 0 ... 6 0000010
18.13 Too long start op Sets the operation of this
protection.
Off, Stop-Manual,
Stop-Automatic,
Indication, Fast ramp
Off
7.17.19 Auto restart protection
Auto restart protection
Auto restart protection has these parameters:
Parameter Description Setting range Default value
18.14 Auto restart max delay Max restart time in seconds 2 ... 3600 s 3600 s
18.15 Auto restart time-out out Specifies the Event groups this
protection belongs to.
Eventgroup 0 ... 6 0000010
1816 Auto restart time-out op Sets the operation of this
protection.
Off, Stop-Manual,
Stop-Automatic,
Indication
Off
7.17.20 HMI failure protection
This protection senses errors in communication between
the Softstarter and the HMI, while the Softstarter is in
local control.
If the communication with the HMI is lost for more than
approximately 600 ms this protection is on.
This protection has a special action in addition to the
common types of operation:
Stop HMI control - stop the local control and change to
remote control i.e digital input or Fieldbus.
HMI failure protection has these parameters:
Parameter Description Setting range Default value
19.01 HMI failure out Identifies the Event groups this
protection is part of.
Eventgroup 0 ... 6 0000010
19.02 HMI failure op Sets the operation of this
protection.
Off, Stop-Manual,
Stop-Automatic,
Indication, Stop HMI
control
Stop-Manual
7